TSM-95129N
Revised 01-97
Section 15
TM
SM Series TANKTEND Systems
(00-02-2019)
Installation and Operation Instructions
Models: SM1, SM1VR, SM2, SM2VR, SM3, SM3VR, SM4, SM4VR
®
FRANK W.
MFR.
Please read the following information before installing. A visual inspection of this product for damage during shipping is recommended
before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.
GENERAL INFORMATION
Mounting Dimensions
SM1 / SM1VR (1-Tank Monitoring Systems)
14 in. (355 mm)
WARNING
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT
14 in.
(355 mm)
✔ Disconnect all electrical power to the machine.
1-1/2 in.
✔ Make sure the machine cannot operate during installation.
(38 mm)
1/4 in.
✔ Follow all safety warnings of the machine manufacturer.
(6 mm) dia.
4-places
✔ Read and follow all installation instructions.
Mounting Holes
1-1/2 in. (38 mm)
3 in.
(76 mm)
The SM Series System can monitor above or below ground,
single or multi-tank systems (4 tanks maximum). The SM Series
includes BGT1 gage (s) in a wall mounting panel. The SMVR series
includes a vapor recovery option that compensates for gas blankets or
head pressure caused by vapor recovery storage systems.
SM2 / SM2VR (2-Tank Monitoring Systems)
*
*
*
25-3/8 in. (645 mm)
14 in.
(355 mm)
The SM includes a push-button actuated electrical pump assembly, that
supplies the air to clear sensing lines for current readings. Pump oper-
ating voltages available are 120 or 230 VAC (see below).
2-1/2 in.
1/4 in.
(6 mm) dia.
(63 mm)
SM Series Specifications
Panel: Hollow wall mount, cold rolled steel, painted.
Shipping Weight (P100 Pump included):
SM1: 27 lb. (12.25 kg) approximately.
SM2: 44 lb. (20 kg) approx.
SM3: 54 lb. (24.5 kg) approx.
SM4: 65 lb. (29.5 kg) approx.
Shipping Dimensions for All Models (P100 Pump included):
40 x 9 x 15-3/4 in. (1016 x 229 x 400 mm).
4-places
Mounting Holes
1-3/16 in.
(30 mm)
3 in.
(76 mm)
SM3 / SM3VR (3-Tank Monitoring Systems)
36 in. (914 mm)
14 in.
(355 mm)
SMPA and SMPA230 Pump Assemblies
Operating Voltage: 120 VAC (SMPA); 230 VAC (SMPA230).
Power Cable: Insulated, 16 AWG (1.5 mm2) x 8 ft. (2.4 m).
Case: Weatherproof enclosure; painted.
2-1/2 in.
(63 mm)
1-3/16 in.
(30 mm)
1/4 in. (6 mm) dia.
Shipping Weight: 10 lbs. (4.53 kg).
Shipping Dimensions: 12 x 12 x 10 in. (305 x 305 x 254 mm).
3 in.
4-places–Mounting Holes
(76 mm)
SM4 / SM4VR (4-Tank Monitoring Systems)
SMPA and SMPA230 Mounting Dimensions
39-1/2 in. (1 m)
1-1/4 in.
(32 mm)
14 in.
(355 mm)
12-1/4 in.
(311 mm)
9/32 in.
10 in.
(7 mm) dia.
6-places
2-1/2 in.
(63 mm)
(254 mm)
1/4 in. (6 mm) dia.
1-3/16 in.
(30 mm)
3 in.
3 in.
3 in.
5/8 in.
4-places–Mounting Holes
4-1/8 in.
(76 mm)
(76 mm)
(76 mm)
(16 mm)
(105 mm)
*
Mounting dimensions also apply for vertical mounting configurations.
INSTALLATION Continued
Installing the CKBO Check Valve
Fig. 3 SM Panel Tubing Configuration
The optional CKBO check valve is designed
to prevent product from backing up into the
gage(s). We recommend installing the
CKBO valve at top of the tank plug as
follows (refer to Detail C):
(SM2 Model shown)
Detail C
Tubing
1/4 NPTM
straight
fitting
Valve
Flat
1. Determine a location for the valve.
Use of sealant on all fitting
FEET
FEET
Check
Valve
T
A
N
K
MURPHY
MURPHY
threads is strongly suggested.
LEVELGAGE
LEVELGAGE
2. Attach CKBO to the tank plug
using wrench on valve flats.
See markings on the valve body
for positioning.
1/2 NPTM to
1/4 NPTF
Reducer
1/4 NPTM
straight fitting
Ferrule
Hole Plug
Ferrule nut
UTKN Tank Plug
or tank top
3. Attach tubing to CKBO as shown.
Securely tighten all fittings.
To Pump
Assembly
All connections must be air tight.
Installing the SMPA/SMPA230 Pump Assembly
The pump assembly should be installed near the SM or SMVR panel.
Connect the pump as follows (refer to Fig. 3 and 4 also see Detail D):
To Tank 2 Plug
Sensor Fitting
To Tank 1 Plug
Sensor Fitting
To Tank 1 Plug
Vapor Recovery
Fitting
To Tank 2 Plug
Vapor Recovery
Fitting
1. Before connecting the tubing from the SM or
Detail D
SMVR panel to the pump assembly, make sure
the tubing reaches the pump assembly
Pump
Panel
sensor fitting.
Fig. 4 Pump Assembly
2. Connect the end of the tubing to the sen-
sor fitting as shown at right (Detail D).
Tubing should be continuous length
without splices.
3. The pump assembly includes a power
cable, 16 AWG (1.5 mm2), 8 ft. (2.4 m)
long. Connect the cable to 120 VAC or
230 VAC power source.
Sensor Fitting
Ferrule
Power
Cable
Pressure SWICHGAGE®
Compression
Nut
Tubing
PSI
The pump assembly has a pressure SWICHGAGE®
kPa
PRESSURE
with low and high pressure set points. When the gage pointer reaches the
low pressure set point, the pump starts to built up purge pressure. When the
pointer reaches the high set point, sufficient volume is reached stopping the
pump. The set points are factory pre-set for your convenience.
High trip point
adjustment
Low trip point
adjustment
Resetting the Pointer
120 VAC or 230 VAC
CAUTION: SM and SMVR models are precalibrated in feet of
static pressure above gage connection. Pointer MUST be reset to zero.
Tubing to SM Panel
After the SM/SMVR complete system has been connected, reset the pointer
for proper level indication, proceed as follows
Detail E
(see Fig. 5 and Detail E):
Fig. 5
1. Determine actual product level by any reliable
means and record this value.
2. Very carefully remove the retaining ring
Turn to Raise
Snap Ring
the Pointer
guarding against its spring-action, it can
cause injuries. Remove the lens also.
FEET
FEET
Pointer
3. Carefully hold the pointer, as shown at
right, making sure not to bend it.
4. With a small screwdriver, turn the setting
MURPHY
LEVELGAGE
MURPHY
LEVELGAGE
Turn to Lower
the Pointer
Read Button
screw to corresponding stick reading value
recorded in step 1.
UNLEADED
UNLEADED
Clockwise to raise the pointer — counter clockwise to lower the pointer.
5. Replace the lens and snap ring.
3
INSTALLATION Continued
Operation Sequence
Fig. 6
IMPORTANT: Make sure SM Series system is completely
installed and operative. Check that all connections are air tight.
Snap Ring
1. Make sure that the pump assembly is connected to a power source,
either 120 VAC or 230 VAC according to the pump model used.
2. Depress the read button, located next to the gage(s) and hold until the
gage pointer stops traveling across the scale. See Fig. 6, at right.
3. When pointer stops release the read button to allow pointer to settle.
4. The value observed in the dial of the gage, is the level of the tank.
5. Perform this operation as necessary for each tank to be checked.
FEET
FEET
Pointer
MURPHY
LEVELGAGE
MURPHY
LEVELGAGE
Read Button
UNLEADED
UNLEADED
Service Parts and Accessories
UTKN2:
2 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings).
2 NPTM tank plug less tubing (includes fittings).
UTKN2LT:
UTKN4:
4 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings).
4 NPTM tank plug less tubing (includes fittings).
UTKN4LT:
UTKN4VR:
UTKN4VRLT:
SMPA:
4 NPTM tank kit for vapor recovery (tubing and fittings included).
4 NPTM tank plug for vapor recovery– less tubing (includes fittings).
Pump assembly for 120 VAC.
SMPA230:
05090051:
CKBO:
Pump assembly for 230 VAC.
Pressure SWICHGAGE® instrument with low and high pressure limit contacts, 15 psi scale.
Check Valve assembly–prevents product from backing up into gage.
1/2 NPTM x 1/4 NPTF reducing bushing–for CKBO valve mounting.
1/4 in. (6 mm) dia. 316 stainless steel tubing/ft. (probe).
85-01-0405:
85-01-0402:
85-01-0403:
86-03-0405:
85-03-0407:
1/4 in. (6 mm) dia. poly tubing/ft. (sensing line).
1/4 x 1/4 male hex nipple kit–for connecting tubing line to tank top.
1/4 x 1/4 male hex fitting kit–for connecting tubing or probe line to the tank top.
Warranty
A two year limited warranty on materials and workmanship is provided with this Murphy product.
Details are available on request and are packed with each unit.
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
■ Murphy de México, S.A. de C.V.
■ Frank W. Murphy, Ltd.
®
FRANK W.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P.; México 78384
tel. +52-48-206264 fax +52-48-206336
e-mail [email protected]
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
tel. +44 1722 410055 fax +44 1722 410088 tlx 477088
e-mail [email protected]
MFR.
Since 1939
■ Frank W. Murphy Manufacturer
P.O. Box 470248; Tulsa, Oklahoma 74147; USA
tel. (918) 627-3550 fax (918) 664-6146
e-mail [email protected]
■ Frank W. Murphy Pte., Ltd.
■ Murphy Switch of California
26 Siglap Drive; Republic of Singapore 456153
tel. +65 241-3166 fax +65 241-8382
e-mail [email protected]
■ Murphek Pty., Ltd.
1620 Hume Highway; Campbellfield, Vic 3061; Australia
tel. +61 3 9358-5555 fax +61 3 9358-5558
P.O. Box 900788; Palmdale, California 93590; USA
tel. (805) 272-4700 fax (805) 947-7570
e-mail [email protected]
■ Frank W. Murphy France
tel. +33 1 30 762626 fax +33 1 30 763989
■ Frank W. Murphy Southern Division
P.O. Box 1819; Rosenberg, Texas 77471; USA
tel. (281) 342-0297 fax (281) 341-6006
e-mail [email protected]
Printed in U.S.A.